ANALISIS PERBANDINGAN KINERJA MEDIUM VOLTAGE VARIABLE SPEED DRIVE PADA KONFIGURASI OPERASI TUNGGAL DAN OPERASI GANDA MOTOR INDUKSI TIGA FASA

ADIBOWO, SISWO (2026) ANALISIS PERBANDINGAN KINERJA MEDIUM VOLTAGE VARIABLE SPEED DRIVE PADA KONFIGURASI OPERASI TUNGGAL DAN OPERASI GANDA MOTOR INDUKSI TIGA FASA. Masters thesis, UNIVERSITAS GLOBAL JAKARTA.

[thumbnail of SISWO ADIBOWO.pdf] Text
SISWO ADIBOWO.pdf

Download (3MB)

Abstract

The utilization of a single Medium Voltage Variable Speed Drive (MV-VSD) to
operate more than one induction motor in a medium-voltage pumping system is a
potential approach to improving asset utilization and operational flexibility in
water treatment plants. Conventionally, one MV-VSD is used to drive a single motor
coupled to one pump. However, under certain operating conditions, a single MVVSD can be utilized to operate two motors, thereby increasing production capacity
without requiring an additional drive. Nevertheless, the feasibility of this
configuration must be verified through field measurements to ensure that power
quality and energy efficiency remain within acceptable operating limits and do not
adversely affect system reliability. This study aims to compare the operating
characteristics of a single configuration (1 MV-VSD–1 motor–1 pump) and a dual
configuration (1 MV-VSD–2 motors–2 pumps) in a 3.3 kV medium-voltage
distribution system. An experimental quantitative method was employed using
direct measurements under actual operating conditions. Data were collected using
a Fluke 1738 Power Logger installed at the input side of the MV-VSD after the
system reached steady-state operation. The parameters analyzed included power
factor, Total Harmonic Distortion of Current (THD-I), electrical energy
consumption, water production volume, and Specific Energy Consumption (SEC)
as an indicator of energy efficiency. The measurement data were validated to ensure
consistency and reliability, then processed using descriptive-comparative analysis
and compared with the power quality criteria adopted in this study. The results
indicate that the single configuration achieved a power factor of 0.96, while the
dual configuration achieved approximately 0.90. Although a slight reduction in
power factor was observed in the dual configuration, the value still represents
satisfactory operating performance. In terms of power quality, the THD-I value of
the single configuration was 6.55%, whereas the dual configuration recorded
5.22%. These results indicate that the dual configuration did not increase current
harmonic distortion; instead, it produced a lower THD-I than the single
configuration. Both values remained within the operational criteria adopted in this
study. The SEC analysis showed that the dual configuration was capable of
producing a higher volume of treated water while maintaining competitive energy
utilization compared with the single configuration. However, the interpretation of
the SEC results was limited by the available water production data interval and
recording format. Overall, the findings demonstrate that the dual operating
configuration is feasible for pumping applications employing motors with similar
specifications and compatible load characteristics, provided that appropriate
protection coordination, load sharing, and continuous operational monitoring are
implemented to ensure system reliability and safe operation.
Keywords: Medium Voltage Variable Speed Drive, three-phase induction motor,
single operation, dual operation, power factor, THD-I, Specific Energy
Consumption.