ID’HA NORGIYANTO, ARFAN ANALISIS PEMILIHAN MATERIAL ISOLATOR PADA STUDI KASUS JARINGAN SUTT 150 KV RUAS PEGANGSAAN - NEW PLUMPANG PADA DAERAH KOROSIF / PINGGIR PANTAI. [Skripsi]
CD_Skripsi_ANALISIS PEMILIHAN MATERIAL ISOLATOR PADA STUDI KASUS JARINGAN SUTT 150 KV RUAS PEGANG.pdf
Download (3MB)
Abstract
The 150 kV Pegangsaan–New Plumpang overhead transmission line (OHL) is a 6.2
km transmission corridor consisting of 23 towers, located in North Jakarta,
Indonesia. This area is characterized by a highly corrosive coastal environment and
very heavy pollution levels, which significantly affect the performance and
reliability of transmission line insulation. Based on lightning strike records from
the Fault and Lightning Location System (FALLS), the average lightning intensity
in this corridor reaches approximately 80 strikes per year. Furthermore, disturbance
data obtained from the Fault Outage Information System (FOIS) for the period
2015–2024 indicate that six transmission outages have occurred. Detailed analysis
of the disturbance on 29 February 2024 identified an insulator flashover at tower
TD6, which was still equipped with glass insulators. This study aims to identify the
causes of lightning strike disturbances and determine the appropriate type and
specifications of insulators for the 150 kV Pegangsaan–New Plumpang overhead
transmission line, considering environmental conditions and pollution levels in the
area. The data collection methods include visual observation of insulators in
resisting pollutants, insulation resistance testing, and economic analysis. The results
indicate that polymer insulators exhibit superior performance compared to glass
and ceramic insulators in terms of insulation strength, resulting in lower leakage
current and higher resistance to flashover. Therefore, polymer insulators are more
suitable for use in highly polluted coastal areas. The economic analysis shows that
polymer insulators are more cost-efficient, with maintenance cost savings of 70.6%
compared to ceramic insulators and 71.2% compared to glass insulators in terms of
maintenance and replacement costs. This study provides recommendations for
optimal insulator specifications to enhance the reliability and operational efficiency
of the 150 kV Pegangsaan–New Plumpang transmission line.
Keywords: Polymer insulator, ceramic, glass, pollution, SUTT 150kV, flashover