SOLIKIN, SOLIKIN ANALISIS PENERAPAN PROTEKSI POLA NON-CASCADE AKIBAT GANGGUAN PADA BUSBAR 20KV. [Skripsi]
Skripsi solikin 2025 JGU_Final_CD.pdf
Download (1MB)
Abstract
Short-circuit faults on 20 kV busbars can generate high fault currents and
potentially accelerate transformer insulation degradation if not promptly cleared.
In conventional protection systems, 20 kV busbar protection generally applies a
cascade protection scheme based on time-graded coordination between feeder
relays and incoming relays. This scheme has limitations in terms of relatively long
fault clearing times, which increase the risk of equipment damage. This study aims
to analyze the characteristics of 20 kV busbar faults and to evaluate the
performance of protection systems before and after the implementation of a non-
cascade protection scheme at the GIS 150 kV Menteng substation. The research
method employed is a descriptive technical analysis with a case study approach,
based on fault disturbance records, relay characteristic testing, and functional
testing using secondary injection. The results indicate that 20 kV busbar faults
produce short-circuit current 11 kA, with relatively long clearing times under the
cascade protection scheme. After the implementation of the non-cascade protection
scheme, the operating time of the 20 kV incoming relay was significantly reduced
without compromising protection selectivity. Therefore, the non-cascade protection
scheme is proven to enhance protection system reliability, accelerate fault clearing,
and reduce the impact of through fault current on power transformers.
Keywords: 20 kV Busbar, Non-cascade Protection, Overcurrent Relay, GIS
Substation.