Search for collections on Jakarta Global University

OPTIMASI AKURASI LOW-COST PHASOR MEASUREMENT UNIT (PMU) MENGGUNAKAN PEMROSESAN DATA BERBASIS FPGA

Hasrat Wati Gulo, Niat OPTIMASI AKURASI LOW-COST PHASOR MEASUREMENT UNIT (PMU) MENGGUNAKAN PEMROSESAN DATA BERBASIS FPGA. [Skripsi]

[thumbnail of Skripsi Niat_File CD.pdf] Text
Skripsi Niat_File CD.pdf

Download (3MB)

Abstract

A low-cost Phasor Measurement Unit (PMU) is an economical alternative
for power system monitoring; however, its measurement accuracy is still affected
by limitations in the digital data processing stage, leading to deviations in
synchrophasor parameters, particularly Total Vector Error (TVE) and Frequency
Error (FE). This study aims to improve the accuracy of a low-cost PMU through
digital calibration using gain parameters based on a Field Programmable Gate
Array (FPGA), as well as to compare the system architecture and phase-angle
visualization with a Real PMU. The research employed a Digital Signal Processing
(DSP) approach through a Linearization method with gain correction. The gain
value was obtained by comparing the low-cost PMU's measurement results against
a multimeter as a reference, and was then implemented in the Digital Signal
Conditioning (SIGCOND) module using the fixed-point method. Evaluation was
carried out based on IEEE C37.118.1a-2014 using voltage TVE, current TVE, and

FE parameters, along with a comparison of the system architecture and phase-
angle visualization with a Real PMU. The results show that gain correction

improved measurement accuracy. The voltage TVE after calibration ranged from
0.12–0.32%, while the current TVE reached 0% across all phases, thereby meeting
the maximum limit of 1% set by IEEE C37.118.1a-2014. The FE value after
calibration decreased to approximately ±0.01 Hz; however, it could not be
confirmed whether this met the IEEE limit of 0.005 Hz, since the frequency display
on the prototype only supports two decimal places. The Real PMU has a more
complete architecture and visualization, while the low-cost PMU offers a simpler
design. Future research is recommended to improve the resolution of the frequency
display, evaluate ROCOF using a reference PMU, and conduct testing on power
distribution systems under actual operating conditions.

Keywords: Low-cost PMU, FPGA, DSP, Linearization , Gradient , Measurement
Accuracy, IEEE C37.118.1a-2014.

Tipe Dokumen: Skripsi
Tipe: Skripsi
Jurusan: Program Studi Teknik Elektro
Depositing User: Dept Perpustakaan Jakarta Global University
Date Deposited: 23 Oct 2026 04:23
Last Modified: 23 Oct 2026 04:23
URI: https://digilib.jgu.ac.id/id/eprint/798