ABSTRACT
Storage temperature is a critical factor in maintaining the stability and
quality of pharmaceutical products. Warehouse B of PT X employs a vertical rack
storage system with two distinct temperature zones within a single storage area:
racks A–G, levels 1–8 (requirement ≤ 30°C), and locators B, C, K, L, M, levels 1–
3 (requirement 20–25°C), potentially causing vertical temperature variation. This
study aimed to analyze the vertical temperature distribution, determine hot - cold
spots, and evaluate the conformity of the temperature mapping results with United
States Pharmacopoeia (USP) Chapter 659 and Farmakope Indonesia (Indonesian
Pharmacopoeia) 6th Edition standards. A descriptive observational method with an
evaluative approach was applied through temperature mapping, analyzed using
parametric statistical tests (normality, homogeneity, one-way ANOVA, and
Bonferroni post hoc tests). Results showed a significant vertical temperature
difference in racks A–G (p = 0.000), with a consistent hot spot at the High level
(T7) and a consistent cold spot at the Low level (T6 or T3) across all racks. In
contrast, locators B, C, K, L, M showed no significant difference between levels (p
= 0.069) due to effective AHU air circulation, with hot spots generally at the High
level and cold spots varying across points. The Mean Kinetic Temperature (MKT)
was 24.85°C for Section 1 and ranged from 23.86–24.00°C for Section 2, both
within acceptance limits, with excursion durations not exceeding 24 hours. The
storage conditions of Warehouse B at PT X were concluded to meet the qualification
acceptance criteria of USP Chapter 659 and Farmakope Indonesia 6th Edition.
Keywords: Temperature Mapping, Vertical Temperature Distribution,
Pharmaceutical Warehouse, USP, Farmakope Indonesia 6th Edition