Search for collections on Jakarta Global University

OPTIMALISASI OPERASI SISTEM PEMOMPAAN MULTIMOTOR DENGAN MEMPERTIMBANGKAN RUGI DAYA PADA KABEL FEEDER TEGANGAN MENENGAH

Pauji, Achmad (2026) OPTIMALISASI OPERASI SISTEM PEMOMPAAN MULTIMOTOR DENGAN MEMPERTIMBANGKAN RUGI DAYA PADA KABEL FEEDER TEGANGAN MENENGAH. Masters thesis, UNIVERSITAS GLOBAL JAKARTA.

[thumbnail of ACHMAD PAUJI.pdf] Text
ACHMAD PAUJI.pdf

Download (2MB)

Abstract

The clean-water distribution pumping system at IPA Pulogadung, East Jakarta,
operates nine medium-voltage induction motor-pump units rated 340–950 kW in
parallel to meet a varying flow demand. The same target flow can be achieved through
different pump combinations, yet each configuration produces different feeder
currents, cable power losses, voltage drops, energy consumption, and operating costs.
This study aims to optimize the operation of a multi-motor pumping system while
considering power losses in the medium-voltage feeder cables, in order to obtain the
configuration with the lowest electricity operating cost at an equivalent hydraulic
service. The analysis is based on actual electrical data from SCADA, power meters,
and operation logs under non-peak and peak conditions. Cable resistance is corrected
for the operating temperature, power loss is computed as a quadratic function of
current, and system efficiency is evaluated within the source–feeder–motor boundary.
Thirty-one structural combinations of five candidate units (Pumps 1B, 2B, 3B, 4B, and
2S) are screened against hydraulic and electrical limits, then optimized for energy and
cost using the PLN time-of-use tariff. The results indicate an optimal configuration of
2B+3B under non-peak and 1B+2B+3B under peak conditions. At an equivalent
hydraulic service, duration, and tariff, this configuration reduces the model energy by
11.84% and the operating cost by 11.79% (from IDR 50,625,459 to IDR 44,655,999
per day) compared with the existing operation. The feeder cable loss is about 64.40
kWh per day, or 0.15% of the daily energy of the analysed unit group; it is therefore
not the primary source of the savings but remains necessary as an objective-function
component and a source-side cost comparator. Because the cost saving exceeds the 5%

threshold, the alternative hypothesis is supported within the model space. A Node-
RED-based digital twin prototype was developed as a human-in-the-loop advisory

dashboard to generate, screen, and rank candidates. These results represent potential
savings within the model space and require verification through trial operation before
implementation.

Keywords: cable power loss, energy cost optimization, feeder cable, multi-motor
pumping system, variable speed drive

Tipe Dokumen: Thesis (Masters)
Tipe: Thesis
Jurusan: Program Studi S2 Elektro
Depositing User: Dept Perpustakaan Jakarta Global University
Date Deposited: 23 Oct 2026 01:45
Last Modified: 23 Oct 2026 06:39
URI: https://digilib.jgu.ac.id/id/eprint/769

Actions (login required)

View Item
View Item