UMBARAN, WISNU (2026) PENGEMBANGAN MODEL HEALTH INDEX TRANSFORMATOR MEDIUM VOLTAGE BERBASIS DYNAMIC NON-LINEAR PENALTY SYSTEM DAN MULTITIER TRIGGERING PROTOCOL UNTUK MITIGASI RISIKO ISO 55001. Masters thesis, UNIVERSITAS GLOBAL JAKARTA.
WISNU UMBARAN.pdf
Download (1MB)
Abstract
Medium-voltage distribution transformers at water treatment installations (IPA
Pejompongan 2 and IPA Buaran) face operational failure risks that impact clean
water production continuity. Conventional Health Index (HI) models based on the
Weighted Sum Model (WSM) are prone to a cancellation effect bias, where one
excellent parameter masks the risk posed by another critical parameter. This study
aims to develop a Dynamic Penalty Factor System that corrects the Linear HI
through a penalty factor based on critical condition scores from Dissolved Gas
Analysis/DGA (acetylene detection) and Dielectric Response Analysis/DIRANA
(paper insulation moisture content), and to design a Multi-Tier Conditional
Triggering Protocol for maintenance scheduling efficiency. Four transformer units
(TB1, TB2, TP1, TP2) were tested using Breakdown Voltage (BDV), DGA, and
DIRANA. Parameter weights were determined through the Analytic Hierarchy
Process (AHP): DGA 40%, DIRANA 35%, BDV 25%. The results show that the
conventional linear model classified TP1 as Very Good (Linear HI = 86%), but the
Dynamic Penalty Factor System corrected this to 77.4% (Good category) after
detecting a paper insulation moisture content of 3.2% (Moist category). A similar
correction occurred for TB1, from 80% to 72%, due to detected acetylene gas (1.43
ppm) indicating early arc discharge. Monte Carlo simulation (20,000 iterations)
validated the model's stability against measurement uncertainty, with
computational validation reaching 100% agreement across 24 tested parameters.
This model provides technical-economic justification for asset management, with
estimated financial loss potential from unplanned outages of Rp206,496,000 per
hour at IPA Pejompongan 2 and Rp295,920,000 per hour at IPA Buaran. This
research contributes to the development of a transformer asset risk management
framework aligned with ISO 55001, providing more accurate early warning than
conventional models.
Keywords: Health Index, transformer, Dynamic Penalty Factor, Dissolved Gas
Analysis, ISO 55001
| Tipe Dokumen: | Thesis (Masters) |
|---|---|
| Tipe: | Thesis |
| Jurusan: | Program Studi S2 Elektro |
| Depositing User: | Dept Perpustakaan Jakarta Global University |
| Date Deposited: | 23 Oct 2026 02:25 |
| Last Modified: | 23 Oct 2026 06:53 |
| URI: | https://digilib.jgu.ac.id/id/eprint/779 |